TeSys D Contactor, 3-Poles (3 NO), 50A, 24V AC Coil, Non-Reversing
TeSys Deca contactor, 3 poles (3NO), for motor control applications up to 50A/690V AC-3/3e (22kW@400V). It provides a 24V 50/60Hz AC coil, 1NO+1NC built-in auxiliary contacts (NC mirror certified), power connection by screw terminals, control connection by screw clamp terminals. For operating rates until 3600 cycles/hour and environments until 60°C, it procures high reliability and durability. Compact (75mm width), DIN-rail mounting or screw fixing. Multi-standards certified (IEC, UL, CSA, CCC, EAC, Marine), Green Premium compliant (RoHs/Reach). Range TeSys Range of product TeSys Deca Product or component type Contactor device short name LC1D contactor application Resistive load Utilisation category AC-1AC-2
AC-3e
AC-1 Poles description 3P [Ue] rated operational voltage Power circuit: <= 690 V AC 25...400 Hz [Ie] rated operational current 50 A (at <60 °C) at <= 440 V AC AC-3e for power circuit
80 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
65 A (at <60 °C) at <= 440 V AC AC-3 for power circuit [Uc] control circuit voltage 120 V AC 50/60 Hz Motor power kW 30 kW at 440 V AC 50 Hz (AC-3)
30 kW at 500 V AC 50 Hz (AC-3)
33 kW at 660...690 V AC 50 Hz (AC-3)
15 kW at 220...230 V AC 50 Hz (AC-3)
11 kW at 400 V AC 50 Hz (AC-4)
30 kW at 1000 V AC 50 Hz (AC-3)
22 kW at 380...400 V AC 50 Hz (AC-3e)
25 kW at 415 V AC 50 Hz (AC-3e)
30 kW at 440 V AC 50 Hz (AC-3e)
30 kW at 500 V AC 50 Hz (AC-3e)
33 kW at 660...690 V AC 50 Hz (AC-3e)
15 kW at 220...230 V AC 50 Hz (AC-3e)
30 kW at 1000 V AC 50 Hz (AC-3e)
30 kW at 380...400 V AC 50 Hz (AC-3) Motor power hp 15 hp at 200/208 V AC 60 Hz for 3 phases motors
15 hp at 230/240 V AC 60 Hz for 3 phases motors
40 hp at 460/480 V AC 60 Hz for 3 phases motors
40 hp at 575/600 V AC 60 Hz for 3 phases motors
5 hp at 115 V AC 60 Hz for 1 phase motors
10 hp at 230/240 V AC 60 Hz for 1 phase motors Compatibility code LC1D Pole contact composition 3 NO Protective cover With [Ith] conventional free air thermal current 10 A (at 60 °C) for control circuit
80 A (at 60 °C) for power circuit Irms rated making capacity 1000 A at 440 V for power circuit conforming to IEC 60947
140 A AC for control circuit conforming to IEC 60947-5-1 Rated breaking capacity 1000 A at 440 V for power circuit conforming to IEC 60947 Associated fuse rating 100 A gG at <= 690 V coordination type 2 for power circuit
10 A gG for control circuit conforming to IEC 60947-5-1
125 A gG at <= 690 V coordination type 1 for power circuit Power dissipation per pole 3.7 W AC-3e
9.6 W AC-1
6.3 W AC-3 [Ui] rated insulation voltage Power circuit: 600 V CSA certified
Power circuit: 600 V UL certified
Control circuit: 690 V conforming to IEC 60947-1
Power circuit: 690 V conforming to IEC 60947-1
Control circuit: 600 V CSA certified
Control circuit: 600 V UL certified Overvoltage category III [Uimp] rated impulse withstand voltage 6 kV conforming to IEC 60947 Safety reliability level B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1 Mechanical durability 6000000 cycles Control circuit type AC at 50/60 Hz Coil technology Without built-in bidirectional peak limiting diode suppressor Control circuit voltage limits 0.85...1.1 Uc (-40…60 °C):operational AC 60 Hz
1...1.1 Uc (60…70 °C):operational AC 50/60 Hz
0.3...0.6 Uc (-40…70 °C):drop-out AC 50/60 Hz
0.8...1.1 Uc (-40…60 °C):operational AC 50 Hz Inrush power in VA 140 VA cos phi 0.75 (at 20 °C)
160 VA cos phi 0.75 (at 20 °C) Hold-in power consumption in VA 13 VA 60 Hz cos phi 0.3 (at 20 °C)
15 VA 50 Hz cos phi 0.3 (at 20 °C) Heat dissipation 4…5 W at 50/60 Hz for control circuit Operating time 4...19 ms opening
12...26 ms closing Maximum operating rate 3600 cyc/h 60 °C Connections - terminals Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible without cable end
Control circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: flexible without cable end
Control circuit: screw clamp terminals 1 1…2.5 mm² - cable stiffness: flexible with cable end
Control circuit: screw clamp terminals 2 1…2.5 mm² - cable stiffness: flexible with cable end
Power circuit: screw terminals 1 2.5…25 mm² - cable stiffness: rigid
Power circuit: screw terminals 2 2.5…16 mm² - cable stiffness: rigid
Power circuit: screw terminals 1 2.5…25 mm² - cable stiffness: flexible without cable end
Power circuit: screw terminals 2 2.5…16 mm² - cable stiffness: flexible without cable end
Power circuit: screw terminals 1 2.5…25 mm² - cable stiffness: flexible with cable end
Power circuit: screw terminals 2 2.5…10 mm² - cable stiffness: flexible with cable end
Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: rigid
Control circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: rigid Tightening torque Power circuit: 5 N.m - on screw terminal - with screwdriver flat Ø 6 to Ø 8 mm
Control circuit: 1.7 N.m - on screw clamp terminal - with screwdriver pozidriv No 2
Control circuit: 1.7 N.m - on screw clamp terminal - with screwdriver flat Ø 6 mm
Control circuit: 1.7 N.m - on screw clamp terminal - with screwdriver Philips No 2 auxiliary contact composition 1 NO + 1 NC Auxiliary contacts type type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1
type mirror contact 1 NC conforming to IEC 60947-4-1 Minimum switching voltage 17 V for control circuit Minimum switching current 5 mA for control circuit Insulation resistance > 10 MOhm for control circuit Non-overlap time 1.5 ms on de-energisation between NC and NO contacts
1.5 ms on energisation between NC and NO contacts Mounting support Rail Standards EN 60947-5-1
UL 508
IEC 60947-4-1
IEC 60947-5-1 product certifications GOST
GL
DNV
LROS (Lloyds register of shipping)
CCC
RINA
BV
UKCA
UL IP degree of protection IP2X conforming to IEC 60529
IP2X conforming to VDE 0106 Climatic withstand conforming to IACS E10 exposure to damp heat
conforming to IEC 60947-1 Annex Q category D exposure to damp heat Operating altitude 0...3000 m Fire resistance 850 °C conforming to IEC 60695-2-1 Flame retardance V1 conforming to UL 94 Mechanical robustness Vibrations contactor opened (2 Gn, 5...300 Hz)
Vibrations contactor closed (4 Gn, 5...300 Hz)
Shocks contactor opened (10 Gn for 11 ms) Height 122 mm Width 55 mm Depth 120 mm Net weight 1.4 kg Quantity per set Set of 10 Unit Type of Package 1 PCE Number of Units in Package 1 1 Package 1 Height 9.5 cm Package 1 Width 13.2 cm Package 1 Length 14.0 cm Package 1 Weight 1.436 kg Unit Type of Package 2 S02 Number of Units in Package 2 5 Package 2 Height 15 cm Package 2 Width 30 cm Package 2 Length 40 cm Package 2 Weight 7.502 kg Warranty 18 months
Resources
Description supplied by Blackhawk Supply through its current Shopify listing. Product, performance, and health claims are the seller’s and have not been independently verified by StorkScout.